Fire and emergency: inspection and testing
| Item | How often | Basis | Reference | Applies to |
|---|---|---|---|---|
Portable fire extinguishers: routine inspectionBy: Fire protection technicianState notesVIC: for the building owner, mandatory where the item is an essential safety measure in the occupancy permit or maintenance determination (Building Regulations 2018 r.215 to 217), which commonly adopts AS 1851-2012. Elsewhere, and for workplaces that are not the building owner, AS 1851 is the benchmark. Other states have their own building fire-safety schemes (for example the NSW annual fire safety statement), not covered here. |
Every 6 monthsRecharge after every use | Standard | AS 1851-2012 (portable fire extinguishers section)From a published summary of the standard; check the current edition.Compliance Council (secondary), NT Police, Fire and Emergency Services | All workplaces |
Portable fire extinguishers: pressure test / empty and refillBy: Fire protection technicianState notesVIC: for the building owner, mandatory where the item is an essential safety measure in the occupancy permit or maintenance determination (Building Regulations 2018 r.215 to 217), which commonly adopts AS 1851-2012. Elsewhere, and for workplaces that are not the building owner, AS 1851 is the benchmark. Other states have their own building fire-safety schemes (for example the NSW annual fire safety statement), not covered here. |
Every 5 years (typical; 3-6 years depending on type) | Standard | AS 1851-2012From a published summary of the standard; check the current edition.Compliance Council (secondary) | All workplaces |
Fire blanketsBy: Fire protection technicianState notesVIC: for the building owner, mandatory where the item is an essential safety measure in the occupancy permit or maintenance determination (Building Regulations 2018 r.215 to 217), which commonly adopts AS 1851-2012. Elsewhere, and for workplaces that are not the building owner, AS 1851 is the benchmark. Other states have their own building fire-safety schemes (for example the NSW annual fire safety statement), not covered here. |
Every 6 months | Standard | AS 1851-2012From a published summary of the standard; check the current edition.NT Police, Fire and Emergency Services | All workplaces |
Fire hose reelsBy: Fire protection technicianState notesVIC: for the building owner, mandatory where the item is an essential safety measure in the occupancy permit or maintenance determination (Building Regulations 2018 r.215 to 217), which commonly adopts AS 1851-2012. Elsewhere, and for workplaces that are not the building owner, AS 1851 is the benchmark. Other states have their own building fire-safety schemes (for example the NSW annual fire safety statement), not covered here. |
Every 6 months | Standard | AS 1851-2012From a published summary of the standard; check the current edition.NT Police, Fire and Emergency Services | All workplaces |
Fire hydrants and booster inletsBy: Fire protection technicianState notesVIC: for the building owner, mandatory where the item is an essential safety measure in the occupancy permit or maintenance determination (Building Regulations 2018 r.215 to 217), which commonly adopts AS 1851-2012. Elsewhere, and for workplaces that are not the building owner, AS 1851 is the benchmark. Other states have their own building fire-safety schemes (for example the NSW annual fire safety statement), not covered here. |
Every 6 months; hydrostatic test every 5 yearsBooster pumps monthly | Standard | AS 1851-2012From a published summary of the standard; check the current edition.NT Police, Fire and Emergency Services | All workplaces |
Automatic fire sprinkler systemsBy: Fire protection technicianState notesVIC: for the building owner, mandatory where the item is an essential safety measure in the occupancy permit or maintenance determination (Building Regulations 2018 r.215 to 217), which commonly adopts AS 1851-2012. Elsewhere, and for workplaces that are not the building owner, AS 1851 is the benchmark. Other states have their own building fire-safety schemes (for example the NSW annual fire safety statement), not covered here. |
Every month (minimum)Pump-set tests may be more frequent under AS 1851 | Standard | AS 1851-2012From a published summary of the standard; check the current edition.NT Police, Fire and Emergency Services | All workplaces |
Fire detection and alarm systemsBy: Fire protection technicianState notesVIC: for the building owner, mandatory where the item is an essential safety measure in the occupancy permit or maintenance determination (Building Regulations 2018 r.215 to 217), which commonly adopts AS 1851-2012. Elsewhere, and for workplaces that are not the building owner, AS 1851 is the benchmark. Other states have their own building fire-safety schemes (for example the NSW annual fire safety statement), not covered here. |
Every month | Standard | AS 1851-2012From a published summary of the standard; check the current edition.NT Police, Fire and Emergency Services | All workplaces |
Emergency and exit lightingBy: Licensed electricianState notesVIC: for the building owner, mandatory where the item is an essential safety measure in the occupancy permit or maintenance determination (Building Regulations 2018 r.215 to 217), which commonly adopts AS 1851-2012. Elsewhere, and for workplaces that are not the building owner, AS 1851 is the benchmark. Other states have their own building fire-safety schemes (for example the NSW annual fire safety statement), not covered here. Construction sites (VIC): see electrical group - 6-monthly discharge test. |
Every 6 months (function and 90-minute discharge test)Monthly visual check is common practice | Standard | AS/NZS 2293.2:2019From a published summary of the standard; check the current edition.NT Police, Fire and Emergency Services, The Local Guys Test & Tag (secondary) | All workplaces |
Fire and smoke doorsBy: Fire protection technicianState notesVIC: for the building owner, mandatory where the item is an essential safety measure in the occupancy permit or maintenance determination (Building Regulations 2018 r.215 to 217), which commonly adopts AS 1851-2012. Elsewhere, and for workplaces that are not the building owner, AS 1851 is the benchmark. Other states have their own building fire-safety schemes (for example the NSW annual fire safety statement), not covered here. |
Every 6 monthsHorizontal sliding fire doors: 3-monthly operational test | Standard | AS 1851-2012From a published summary of the standard; check the current edition.Futura Fire (secondary) | All workplaces |
Annual Essential Safety Measures Report (AESMR): VICBy: Building owner (or agent)State notesVIC only. Owner must keep ESM inspection/maintenance records and produce AESMRs within 24 hours of request by the municipal building surveyor or chief officer (r.225). |
Every 12 monthsPrepare within 28 days before the anniversary date (13 June for pre-1994 buildings); keep 10 years of reports | Mandatory | Building Regulations 2018 (Vic) r.223, r.224, r.225Victorian Building Authority | All workplaces |
Emergency evacuation exercise (drill)By: Emergency planning committee / chief wardenState notesModel WHS r.43 requires the emergency plan to provide for testing of emergency procedures, including frequency of testing (PCBU sets it). VIC: no general emergency-plan regulation in OHS Regs 2017 (emergency procedures only for specific hazards); AS 3745 is the benchmark. |
At least every 12 monthsMore often for high-risk facilities | Standard | AS 3745-2010; model WHS Reg 43(1)(b)From a published summary of the standard; check the current edition.First 5 Minutes (secondary), Federal Register of Legislation | All workplaces |
Emergency plan reviewBy: PCBU / emergency planning committeeState notesModel WHS r.43 duty to maintain the plan. AS 3745 sets 'defined intervals' without a fixed period. VIC: AS 3745 benchmark only. |
At planned intervals and after exercises, incidents or significant change | WHS statesMandatoryVICStandard | Model WHS Reg 43 (prepare, maintain and implement); AS 3745-2010From a published summary of the standard; check the current edition.Federal Register of Legislation, First 5 Minutes (secondary) | All workplaces |
Warden / emergency control organisation training refresherBy: RTO / emergency trainerState notesNo regulator interval located. |
Not prescribed (annual refresher is common practice)Train new ECO members before they take up duties | Good practice | AS 3745-2010From a published summary of the standard; check the current edition.First 5 Minutes (secondary) | All workplaces |
A planning guide, not legal advice. Intervals are minimums under normal conditions: shorten them where use, environment, damage or a risk assessment calls for it, and follow the current edition of the standard, your regulator's guidance and the manufacturer's instructions. Victoria operates under the Occupational Health and Safety Act 2004 and the OHS Regulations 2017; the other states and territories under the model WHS laws as adopted locally. Items checked 28 October 2026.
Sources
- Federal Register of Legislation: Work Health and Safety Regulations 2011 (Cth), Compilation No. 28 (25/03/2025) - mirrors model WHS Regulations numbering
- Compliance Council (secondary): How often do fire extinguishers need to be inspected?
- NT Police, Fire and Emergency Services: Fire safety measures maintenance checklist (AS 1851-2012)
- Victorian Building Authority: Practice Note ESM-02 Maintenance of Essential Safety Measures
- The Local Guys Test & Tag (secondary): Emergency exit light testing in Melbourne
- Futura Fire (secondary): Fire and smoke door maintenance
- First 5 Minutes (secondary): AS 3745 compliance overview